Model and Its Designation
Precautions for Service Environment Conditions
● Altitude: Not exceeding 2000 m; Seismic intensity: Not exceeding Grade 8
● Ambient air temperature: Ranging from -45°C to +50°C. Relative humidity: Daily average not exceeding 95%, monthly average not exceeding 90%
● Not suitable for installation sites with frequent severe vibrations, nor for sites where water vapor, gases, chemically corrosive deposits, salt mist, dust and dirt that obviously affect the mechanism performance exist, as well as sites with fire or explosion hazards
● Rated SF₆ gas pressure: 0.04 MPa. The SF₆ gas complies with the requirements specified in GB/T12022-2014 Industrial Sulfur Hexafluoride
Technical Parameters
|
Item
|
Unit
|
Technical Parameters
|
|
Rated Voltage
|
KV
|
12
|
|
Rated Frequency
|
Hz
|
50
|
|
Rated Current
|
A
|
630
|
|
Rated Short-Time Withstand Current
|
KA
|
20/25
|
|
Rated Peak Withstand Current
|
KA
|
50
|
|
Rated Short-Circuit Duration
|
s
|
4
|
|
Rated Short-Circuit Making Current
|
KA
|
50
|
|
Theoretical Operation
|
Times
|
10000
|
|
Main Circuit Resistance
|
μΩ
|
≤35
|