ZW8-12 series outdoor high-voltage column vacuum circuit breaker

Product Overview
The ZW8-12 series outdoor high-voltage vacuum circuit breaker is a high-voltage outdoor switching device with a rated voltage of 12kV and three-phase AC 50Hz. It is mainly used for switching on and off load current, overload current, and short-circuit current in rural power grids, urban power grids, and small-scale power systems. The overall structure of the product is a three-phase common-tank type. Three-phase vacuum interrupters are installed in a metal tank, with SMC insulating material used for phase-to-phase insulation and phase-to-ground insulation. The product features reliable performance and high insulation strength. The ZW8-12G is a combined circuit breaker integrated with the ZW8-12 circuit breaker and an isolating switch. It can be used as a breaking switch and is equipped with a self-contained power supply, available with either a built-in PT or an external PT. The operating mechanism of this series is the CT23-type spring operating mechanism, which is available in electric and manual versions. When matched with an intelligent controller, the product can realize functions such as auto-reclosing, dual-power source switching, and current protection, thereby achieving distribution network automation.
Share:
Operating Environmental Conditions
a. Ambient Air Temperature: Upper limit +40℃; lower limit -30℃ (general areas), -40℃ (alpine areas);
b. Altitude: ≤1000m (if higher altitude is required, the rated insulation level shall be correspondingly increased);
c. Wind Pressure: Not exceeding 700Pa (equivalent to a wind speed of 34m/s);
d. Vibration/Seismic Resistance: Seismic intensity not exceeding 8 degrees (Chinese Seismic Intensity Scale);
e. Pollution Degree: Class Ⅲ;
f. Daily Temperature Difference: Not exceeding 25℃
Main Technical Parameters
No. Name Unit Data
1 Rated Voltage KV 40.5
2 Rated Insulation Level (RIL) 1-minute Power Frequency Withstand Voltage (1min PFWV) Dry Type 95
Wet Type 80
Lightning Impulse Withstand Voltage (Peak Value) 185
3 Rated Current A 1250;1600;2000
4 Rated Short-Circuit Breaking Current KA 20;25;31.5
5 Rated Operating Sequence O - 0.3s - CO - 180s - CO
6 Rated Number of Short-Circuit Breaking Operations Times 12
7 Rated Short-Circuit Making Current (Peak Value) KA 50;63;80
8 Rated Peak Withstand Voltage
9 Rated Short-Time Withstand Current 20;25;31.5
10 Rated Short-Circuit Duration S 4
11 Average Opening Speed M/S 1.5±0.2
12 Average Closing Speed 0.7±0.2
13 Contact Closing Bounce Time MS ≤2
14 Three-Phase Closing (Opening) Synchronism Time Difference ≤2
15 Closing Time ≤150
16 Opening Time ≤60
17 Mechanical Life Times 10000
18 Rated Operating Voltage and Rated Voltage of Auxiliary Circuit V DC 110/220
AC 110/220
19 DC Resistance of Each Static Circuit (Excluding Instrument Transformers) μΩ ≤100
20 Allowable Wear Thickness of Moving and Fixed Contacts MM 3
21 Weight KG 800