Notes on Ambient Operating Conditions
Altitude shall not exceed 2000 m; seismic intensity shall not exceed Grade 8.
The ambient temperature for product operation shall range from -40℃ to +50℃; the daily average relative humidity shall not be greater than 90%, and the monthly average relative humidity shall not be greater than 90%.
The product is not suitable for installation sites subject to frequent severe vibrations, nor for sites with water vapor, gaseous chemical corrosive deposits, salt mist, dust and dirt that obviously affect the performance of the mechanism, as well as sites with fire or explosion hazards.
Main Technical Parameters
|
Item
|
Unit
|
Parameters
|
|
Rated Frequency
|
Hz
|
50
|
|
Rated Current
|
A
|
630
|
|
Rated Short-time Withstand Current
|
kA
|
20/25
|
|
Rated Peak Withstand Current
|
kA
|
50
|
|
Rated Short-circuit Duration
|
S
|
4
|
|
Rated Short-circuit Making Current
|
kA
|
50
|
|
Theoretical Operation
|
0-0.3s-CO-180s-CO
|
Circuit Breaker Outline and Mounting Dimensions Drawing