FLN□(SMR6)-12/630-25 Charging cabinet load switch

Product Overview
The FLN□(SMR6)-12/630-25 gas-insulated switchgear load switch complies with the relevant requirements specified in GB/T 3804 High-voltage Alternating Current Load Switches for Rated Voltages from 3.6 kV to 40.5 kV and GB/T 16926 Alternating-current High-voltage Load Switch-fuse Combinations.
Main Circuit: 630 A - 20 kA (4 s), 25 kA (3 s); Mechanical Endurance: 5,000 operationsEarthing Circuit: 20 kA (2 s); Mechanical Endurance: 2,000 operations
Share:
Notes on Ambient Operating Conditions
Altitude shall not exceed 2000 m; seismic intensity shall not exceed Grade 8.
The ambient temperature for product operation shall range from -40℃ to +50℃; the daily average relative humidity shall not be greater than 90%, and the monthly average relative humidity shall not be greater than 90%.
The product is not suitable for installation sites subject to frequent severe vibrations, nor for sites with water vapor, gaseous chemical corrosive deposits, salt mist, dust and dirt that obviously affect the performance of the mechanism, as well as sites with fire or explosion hazards.
Main Technical Parameters
Item Unit Parameters
Rated Frequency Hz 50
Rated Current A 630
Rated Short-time Withstand Current kA 20/25
Rated Peak Withstand Current kA 50
Rated Short-circuit Duration S 4
Rated Short-circuit Making Current kA 50
Theoretical Operation 0-0.3s-CO-180s-CO
Circuit Breaker Outline and Mounting Dimensions Drawing